AAC Code Name List:
Peachbell, Rose, Iris, Pansy, Poppy, Aster, Phlox, Oxlip, Sneezewort, Daisy, Valerian, Laurel, Peony, Tulip, Daffodil, Canna, Goldentuft, Cosmos, Zinnia, Marigold, Hawthorn, Narcissus, Columbine, Carnation, Coreopsis, Gladiolus, Jessamine, Cowslip, Sagebrush, Lupine, Bitterroot, Trillium, Bluebonnet, Dahlia, Syringa, Hyacinth, Mistletoe, Meadowsweet, Orchid, Heuchera, Flag, Verbena, Violet, Nasturtium, Petunia, Cattail, Arbutus, Lilac, Cockscomb, Snapdragon, Magnolia, Hawkweed, Camellia, Bluebell, Larkspur, Goldenrod.
Standards:
ASTM B-231/ BS 215/ BX EN 50182/ IEC 61089/DIN 48201/ CSA C49
AAC conductor Construction:
Aluminum 1350-H19 wires, concentrically stranded.
Overhead transmission bare conductor-Round wire concentric-lay overhead electrical stranded AAC conductor.
AAC conductor application:
AAC conductor Cable is widely used in the overhead power transimission lines and distribution system,and it is one of the main products to form electrified wire network.
Key Benefits: Conductivity of AAC conductor is high,AAC conductor is corrosion resistant.
Description:
AAC Conductor (All Aluminium Conductors) is also known as aluminium stranded conductor. We manufacture this conductor from electrolytically refined aluminium with the purity of minimum 99% aluminium. The spacing between All Aluminium Conductors is short and their supports are close.
These aluminium conductors are made up of one or more aluminium wires strands depending on their usage. These conductors are mainly used in urban areas for electricity transfer. Apart from that, these conductors are also extensively used in coastal area because of their corrosion resistance properties. Apparently, we have gained recognition as one of the prominent AAC Aluminum Conductor Manufacturers and Suppliers.
Standard Specifications:
AAC bare conductors meet or exceed the following ASTM specifications:
B-230 aluminum wires, 1350-H19 for electrical purpose
B-231 aluminum conductors, concentrically lay-stranded
B-400 compact round concentric-lay-stranded aluminum 1350 conductors
We manufacture AAC conductor as per following standards:-BS 215 Part 1,IEC 207, DIN 48201-5,ASTM B231,IS 398 Part
AAC Conductor IEC Standards:
Code number | Area | Number of wires | Wire diameter | Conductor diameter | Linear mass | Rated strength | D.C. resistance at 20oC |
---|---|---|---|---|---|---|---|
mm2 | No. | mm | mm | kg/km | kN | Ω/km | |
16 | 15.9 | 7 | 1.7 | 5.1 | 43.4 | 3.02 | 1.7986 |
25 | 24.2 | 7 | 2.1 | 6.3 | 66.3 | 4.36 | 1.1787 |
35 | 34.4 | 7 | 2.5 | 7.5 | 93.9 | 6.01 | 0.8317 |
50 | 49.5 | 7 | 3 | 9 | 135.2 | 8.41 | 0.5776 |
50 | 48.3 | 19 | 1.8 | 9 | 132.9 | 8.94 | 0.5944 |
70 | 65.8 | 19 | 2.1 | 10.5 | 180.9 | 11.85 | 0.4367 |
95 | 93.3 | 19 | 2.5 | 12.5 | 256.3 | 16.32 | 0.3081 |
120 | 117 | 19 | 2.8 | 14 | 321.5 | 19.89 | 0.2456 |
150 | 147.1 | 37 | 2.25 | 15.8 | 405.7 | 26.48 | 0.196 |
185 | 181.6 | 37 | 2.5 | 17.5 | 500.9 | 31.78 | 0.1588 |
240 | 242.5 | 61 | 2.25 | 20.3 | 671.1 | 43.66 | 0.1193 |
300 | 299.4 | 61 | 2.5 | 22.5 | 828.5 | 52.4 | 0.0966 |